C#使用Modbus-TCP协议读取汇川PLC,Modbus读写是按照MW地址来处理的
【寄存器单位是字WORD,占用两个字节,类似于C#中的ushort(UInt16)】,实际测试发现字符串是按照字节颠倒的
本文封装函数为基础数据类型读写,字节流读写、长字符串读写。
主要封装函数有:
public int WriteValue<T>(int startAddress, T value, out string msg) where T : struct
public int WriteValue(int startAddress, byte[] buffer, out string msg)
public int WriteString(int startAddress, int length, string barcode, out string msg)
public int WriteLongString(int startAddress, string longString, out string msg)
public int ReadValue<T>(int startAddress, out T value, out string msg) where T : struct
public int ReadValue(int startAddress, int length, out byte[] values, out string msg)
public int ReadLongString(int startAddress, int length, out string longString, out string msg)
源程序如下:
using System;
using System.Collections.Generic;
using System.Linq;
using System.Net.Sockets;
using System.Text;
using System.Threading;
namespace InovancePlcDemo
{
/// <summary>
/// 汇川PLC读写地址表
/// 斯内科 20210907
/// </summary>
public class InovanceTcp
{
/// <summary>
/// 是否已连接
/// </summary>
public bool IsConnected;
/// <summary>
/// 字节存放类型,汇川PLC默认为CDAB
/// </summary>
public StoreByteCategory StoreByteCategory { get; set; }
/// <summary>
/// 是否字符串颠倒,相邻两个字符交换位置【比如:ABCD存放是BADC】
/// </summary>
public bool IsStringReverse = true;
string ip;
int port;
/// <summary>
/// TCP客户端对象
/// </summary>
TcpClient msender;
/// <summary>
/// TCP连接成功后生成的发送和接收Session会话对象
/// </summary>
Socket msock;
/// <summary>
/// 记录Modbus的发送和接收数据包事件
/// 第一个参数是发送的数据包,第二个参数是响应的数据包,第三个参数的获取到响应数据包所花费的时间(ms)
/// </summary>
public event Action<byte[], byte[], double> RecordDataEvent;
/// <summary>
/// 汇川PLC的Modbus协议Tcp连接的构造函数(PLC的IP地址、PLC端口号、本机节点)
/// </summary>
/// <param name="ip">IP地址</param>
/// <param name="port">端口号,默认502</param>
/// <returns>实例化一个Modbus协议Tcp连接</returns>
public InovanceTcp(string ip, int port, StoreByteCategory storeByteCategory = StoreByteCategory.CDAB, bool isStringReverse = true)
{
this.ip = ip;
this.port = port;
this.StoreByteCategory = storeByteCategory;
this.IsStringReverse = isStringReverse;
IsConnected = false;
}
/// <summary>
/// 断开连接
/// </summary>
public void DisConnect()
{
msender?.Close();
msock?.Close();
msock?.Dispose();
IsConnected = false;
}
/// <summary>
/// 连接PLC
/// </summary>
public void Connect()
{
if (!IsConnected)
{
msender = new TcpClient(ip, port);
msock = msender.Client;
msock.ReceiveTimeout = 3000;
IsConnected = true;
}
}
/// <summary>
/// 写基本数据类型到PLC,如bool,short,int,uint,float等
/// </summary>
/// <typeparam name="T"></typeparam>
/// <param name="startAddress">起始寄存器地址,以字(WORD)为单位,形如MW32000</param>
/// <param name="value"></param>
/// <param name="msg"></param>
/// <returns></returns>
public int WriteValue<T>(int startAddress, T value, out string msg) where T : struct
{
byte[] datas = new byte[0];
if (typeof(T) == typeof(bool))
{
datas = BitConverter.GetBytes(Convert.ToBoolean(value));
}
else if (typeof(T) == typeof(sbyte))
{
datas = new byte[1] { (byte)Convert.ToSByte(value) };
}
else if (typeof(T) == typeof(byte))
{
datas = new byte[1] { Convert.ToByte(value) };
}
else if (typeof(T) == typeof(short))
{
datas = BitConverter.GetBytes(Convert.ToInt16(value));
}
else if (typeof(T) == typeof(ushort))
{
datas = BitConverter.GetBytes(Convert.ToUInt16(value));
}
else if (typeof(T) == typeof(int))
{
datas = BitConverter.GetBytes(Convert.ToInt32(value));
}
else if (typeof(T) == typeof(uint))
{
datas = BitConverter.GetBytes(Convert.

本文档详细介绍了如何使用C#通过Modbus-TCP协议与汇川PLC进行通信,包括读写基本数据类型、字节流和字符串。代码实现了连接、断开PLC,以及读写不同数据类型的函数,特别处理了字符串的字节顺序和长度问题。